When a safety light curtain has stopped a machine, clearing the beams should not make hazardous motion resume unexpectedly. A restart interlock requires a deliberate reset, and the machine control then requires a separate start action where the risk assessment and applicable design call for it. The reset acknowledges that the protective field is clear and the restart conditions have been reviewed; it is not a production command.

Separate five distinct states

Write the sequence as field interrupted, field clear, reset accepted, machine ready, and motion started. Each transition needs an owner and condition. The light curtain can detect beam interruption, but it usually cannot prove that no one is standing behind it, that tooling is clear, or that downstream contactors returned correctly.

SICK's operating instructions describe restart interlock as preventing automatic restart after the protective device has been triggered. The operator resets the protective device to monitoring status, then starts the machine in a second step. Preserve that separation in the safety controller, HMI messages, and physical controls.

Place reset where the operator can assess the hazard

The reset control should be outside the hazardous area, inaccessible from inside, and located so the operator has a clear view of the protected space. If one position cannot provide full visibility, the design needs another means—such as additional reset locations with a defined inspection procedure, trapped-key logic, presence detection, or guards—rather than assuming a camera or mirror is always adequate.

Prevent operation from a blind spot or while reaching through the light curtain. Label the control by the safety function it resets. Avoid placing unrelated production buttons next to it in a way that encourages automatic or habitual pressing.

Require a valid press-and-release action

A stuck or shorted reset input must not appear as a new deliberate command. Use the device or safety-controller behavior specified for monitored reset, including the required pulse or edge sequence. SICK documentation warns in some configurations that a reset accepted on press alone can be indistinguishable from a short circuit to the supply when standing behind the curtain is possible.

Test a button held during power-up, held while the field clears, jammed mechanically, shorted where the approved test method permits, and operated repeatedly. The result should be no unintended reset and a diagnostic that directs maintenance to the reset circuit.

Reset and start serve different purposes

After reset, indicate “ready” or “reset complete,” not “running.” A separate start command should be required to energize the process when that is the validated operating concept. The start control should follow normal command rules, mode selection, interlocks, and safe-state checks.

Do not implement a software shortcut that converts the reset edge into a one-scan start pulse. It defeats the operator's opportunity to observe the ready state and deliberately command motion. Likewise, do not let an HMI recipe change or automatic sequence resume act as an implicit start after reset unless a specific validated function allows it.

Monitor the final switching devices

External device monitoring, when part of the design, checks the state of downstream contactors or other machine primary control elements. A welded or slow contactor can prevent a valid reset or restart. The light curtain's outputs turning off is not complete evidence that the hazardous energy path opened as intended.

Wire and configure EDM according to the product and safety-controller documentation, using suitable positively guided feedback where required. Test each feedback channel, a contactor that fails to drop, a contactor that fails to return, and a timing fault. Confirm the machine remains inhibited and the fault cannot be cleared by repeatedly pressing reset.

Control what happens after power and mode changes

Loss and return of power, controller restart, safety-device replacement, operating-mode change, and guard opening can all alter reset state. Define whether a new reset is required. A replacement light curtain may have a different default reset configuration, so electrical reconnection alone does not prove the safety function was restored.

Store and verify the configuration checksum, function settings, and wiring. During commissioning, cycle power with the field clear and interrupted. Confirm there is no unexpected motion and that the required reset sequence remains intact.

Test presence behind the curtain

Where a person can pass through and stand inside the safeguarded space, interrupting then clearing the beams does not mean the area is empty. Perform the validation with a test person or permitted target located behind the protective field while the beams are clear. Verify that reset location and supplementary measures prevent restart.

Consider material flow separately. Muting, blanking, or presence-sensing device initiation are specialized functions with additional rules; they should not be approximated by automatically resetting whenever a carton clears the beams.

Capture the full restart evidence

Record beam status, OSSD state, reset input, reset-accepted or ready state, EDM feedback, start command, safety output, final contactor state, and motion. Test normal interruption, a person remaining inside, stuck reset, held start, failed contactor, power recovery, mode change, and controller restart. Observe both sequence and timing.

The operator message should say what action is actually needed: clear the field, inspect the area, press and release reset, resolve EDM fault, or issue start. A generic “safety fault” promotes button pressing rather than informed control.

A trustworthy reset design preserves human intent. Clearing the light curtain removes one obstruction; reset confirms readiness; a separate start requests motion; and feedback confirms that the energy-control hardware responded. Keeping those meanings distinct is the practical defense against unexpected restart.

Sources checked November 4, 2026:

SICK, miniTwin4 operating instructions, restart interlock and external device monitoring:

https://www.sick.com/media/docs/5/75/375/Operating_instructions_miniTwin4_Safety_light_curtain_en_IM0033375.PDF

SICK, miniTwin2 operating instructions, reset followed by separate start:

https://www.sick.com/media/docs/0/10/610/Operating_instructions_miniTwin2_Safety_light_curtain_en_IM0034610.PDF

SICK, restart interlock definition:

https://www.sick.com/us/en/glossary/restart-interlock/g/p501057