A dual-channel guard switch does not change both inputs at the same mathematical instant. Contacts have travel, actuator geometry, debounce, input filtering, and logic execution delay. A discrepancy timer allows that normal skew while detecting a channel that is stuck, broken, or late. If the window is guessed, it either creates nuisance faults or waits too long to diagnose a real failure.
Define discrepancy and sequence separately
Discrepancy time limits how long the two signals may remain in an implausible combination after one channel changes. Sequence checking verifies that both channels pass through the required inactive state before the function becomes active again. A signal that changes out and back while its partner never changes can be a sequence fault even if the final states match.
SICK documentation describes both behaviors for dual-channel evaluation. The controller's exact truth table matters: equivalent contacts, complementary contacts, and semiconductor outputs have different expected states.
Identify the physical cause of skew
Measure from the same physical guard movement. Two separate position switches can operate at different door angles. A coded switch may present two electronic channels with a specified offset. Cable length is rarely the dominant delay, but filters and remote safety I/O can be.
Inspect looseness, actuator overtravel, hinge play, door sag, vibration, and latch force. A wide measured distribution may signal unstable mechanics that should be repaired rather than hidden with a larger timer.
Include the complete signal path
The effective time includes sensor response, input delay, test-pulse behavior, network or module update, and safety-logic execution. SICK notes that logic execution time must be considered in total timing. Obtain values from the exact controller, module, and firmware.
If tested sensors are connected, the configured discrepancy time must account for the test pulse and tolerated pulse delay as specified by the controller. Do not interpret an intentional test pulse as a real channel transition.
Set the window from evidence
Record open and close transitions over many cycles at normal, slow, and forceful operation. Include cold and hot conditions, door misalignment within allowed tolerance, and realistic cable motion. Choose a limit above the credible normal maximum with justified margin, while remaining short enough to meet diagnostic requirements.
Do not copy a value from another door. A heavy sliding guard, small service hatch, and electronic interlock can have different timing even on one machine.
Test both transition directions
Opening must remove the safety enable within the required response even if one channel changes first. Closing may start the discrepancy timer, but it must never restart hazardous motion by itself. The expected reset and restart sequence remains separate.
Test starting with the guard partly open, moving it very slowly through the switching region, bouncing it near the trip point, and opening then closing before the second channel changes. Verify the controller does not accept an invalid shortcut back to active.
Insert realistic single faults
Disconnect channel A, then B. Short each input to its expected supply or reference using an approved safe method. Prevent one mechanical contact from operating, where the test plan permits, and confirm the discrepancy or sequence diagnostic appears. Test cross-circuit detection if claimed by the architecture.
A correct result includes safe output behavior, a useful diagnostic, reset conditions, and no automatic restart after the fault clears. Record which physical input and logical block reported the failure.
Distinguish discrepancy from synchronization
Some functions evaluate two dual-channel pairs and apply a synchronization time between the pairs. SICK distinguishes that from the discrepancy time within one pair. Label parameters by function and channel pair so commissioning engineers do not tune the wrong timer.
For a single guard with two channels, use the guard block intended by the safety-controller manufacturer. Ad hoc timers in standard PLC logic do not replace certified evaluation.
Diagnose nuisance faults without bypassing
When a discrepancy fault occurs, capture both raw channels, evaluated state, timer, guard position, and time. Repeated faults only on closing suggest alignment or latch behavior; faults in both directions may suggest wiring or one slow channel. A fault after washdown may indicate connector ingress.
Do not increase the timer until alarms disappear. Correct mechanics and wiring first, then repeat the measured study. Preserve first-fault evidence because resetting can clear the useful transition history.
Control maintenance changes
Replacement switches can have different actuation points or output delays. Replacing a hinge, latch, or actuator bracket changes the mechanical relationship. After work, inspect alignment and repeat both-channel timing and fault tests.
The validation record should include switch type, wiring mode, expected truth table, timer value, measured distributions, logic-cycle allowance, test-pulse requirements, inserted faults, reset behavior, and stop response. A discrepancy timer is credible only when it reflects normal mechanics and still exposes the abnormal channel it was designed to find.
Verify the configured value in the exported safety report and compare it with the online controller after download. A mismatch between offline project, active logic, and validation record is itself a configuration fault. Include the safety signature or checksum where the platform provides one, and require review after any safety-program revision.
Sources checked November 4, 2026:
SICK, Flexi Soft Safety Designer function blocks and discrepancy timing:
https://www.sick.com/media/docs/3/83/083/operating_instructions_flexi_soft_in_the_safety_designer_configuration_software_en_im0081083.pdf
SICK, Flexi Compact dual-channel evaluation:
https://www.sick.com/media/docs/9/79/279/operating_instructions_8026634_en_im0096279.pdf
SICK, Flexi Soft hardware troubleshooting for discrepancy and sequence errors:
https://www.sick.com/media/docs/0/60/660/operating_instructions_flexi_soft_modular_safety_controller_hardware_en_im0031660.pdf
Illustration note: The accompanying image is an AI-generated concept, not a validated safety circuit, timing trace, or deployment record.